Commander GP User Guide
Issue code: gpxu2
Setting Up the Drive 3-13
Setting up and using Macro 1
The following may require attention in addition to
the settings made in Chapter 2.
Reference selection
Use 0.05 Reference selector to select the required
frequency source, as follows:
0.05 Source Terminal(s)
0 Analog input 1 or 2 which can be
selected using the LOCAL/REMOTE
contact
5 and 6, or 7
1 Analog input 1 5, 6
2 Analog input 2 7
3 (Do not use)
4 Keypad control
5 (Do not use)
Frequency references
Keypad mode
The value of the keypad reference can be read by
displaying the value of 0.35 Keypad reference.
Terminal mode
Frequency reference 1 (terminals 5, 6) is configured
for 0 to 10V signal.
Frequency reference 2 (terminal 7) is configured for
4 to 20mA signal. Loss of the current signal will be
treated as zero reference.
Jog
To use jog, close the JOG SELECT contact
(terminal 26) before closing the RUN FORWARD
contact (terminal 27) or RUN REVERSE contact
(terminal 28).
Jog will occur at 1.5Hz. This value cannot be altered.